Engineered for continuous soft water quality monitoring, Softcontrol Smart provides accurate detection of hard water breakthrough using a fixed alarm threshold of 10% relative to the incoming water hardness.
The compact monitoring unit helps prevent scaling and equipment damage by providing immediate warning whenever water hardness rises above acceptable levels.
Easy installation, reliable operation and low servicing requirements make Softcontrol Smart a cost-effective addition to commercial and industrial water softening systems.
| Dimensions of case | 120 x 80 x 55 mm (B x H x D) |
| Mounting Area Weight | 220 x 300 x 65 mm (B x H x D) (wall mounted) |
| Weight | appr. 500 g |
| Surrounding Temperature | 5°C to 50°C |
| Relative Humidity | 20% to 80% |
| Power Supply | Wall power supply 100 … 240 V / 50 … 60 Hz |
| Power Consumption | 15 V DC, approx. 4 Watt |
| Raw and Soft Water Connections | Branch pipe with connection for PA-tube o.d. 4 mm, i.d. 2 mm, up streamed dirt filter ≤ 0,1 mm recommended |
| Raw and Soft Water Pressure | Minimum 1 bar up to maximum 10 bars |
| Drain | Minimum ø 8 mm, pressure free |
| Quality of Raw and Soft Water | Natural water, free of grease, oil and brine germ content < 5000 CFU/ml |
| Hardness Range Raw Water | 0.18 ppm up to 10.8 ppm, natural water |
| Evaluation of Water Hardness in Soft Water | From 0.018 ppm |
| Operation Time of Sensor | Approx. 6 to 9 months |